Programming
18
Step Comment
CAL 12 High Alarm or Pulse Output Factor - whole numbers.
CAL 13 High Alarm or Pulse Output Factor - digits after the decimal
point.
CAL 12 & 13 program the flow rate above which the high
alarm relay will close. The value can be programmed in the
range 0 to 999,999.
If the scaled pulse output is selected (see CAL0 = 1), then the
value will represent the total per pulse, eg. 5 litres per pulse.
CAL 14 4mA Retransmission - whole numbers.
CAL 15 4mA Retransmission - digits after the decimal point.
CAL 14 to CAL 15 represent the flow rate at which 4mA will
be output. If the 4-20mA retransmission is not installed, these
parameters can be ignored.
CAL 16 20mA Retransmission - whole numbers.
CAL 17 20mA Retransmission - digits after the decimal point.
CAL 16 & 17 are the flow rates at which the output will reach
20mA.
SOFT
Software Version.