Yokogawa 202 Field Mounting Rate Totalizer Uživatelský manuál

Procházejte online nebo si stáhněte Uživatelský manuál pro Počítače Yokogawa 202 Field Mounting Rate Totalizer. Yokogawa 202 Field Mounting Rate Totalizer User Manual Uživatelská příručka

  • Stažení
  • Přidat do mých příruček
  • Tisk

Shrnutí obsahu

Strany 1 -

FIELD MOUNTEDRATE TOTALISERMODEL 202A 2 August 1999

Strany 2

2. SPECIFICATIONGeneralDisplay: LCD, which is continuously powered.Resettable Total: 7 digits with 10mm (0.4") high digits. Resettable from fron

Strany 3 - CONTENTS

OutputsType: Two open collector outputs suitable for driving DCsolenoids or external relays. The outputs provide highand low flow alarms or pulse out

Strany 4

3. PROGRAMMINGThe Model 202A is fully programmable, with all parameters being stored innon-volatile memory.The Program Mode can be entered in the foll

Strany 5 - 1. INTRODUCTION

3.1 PROGRAM STEPSStep CommentCAL 00Pulse Output0 = No pulse output, low and high alarms1 = Scaled pulse output and low alarmCAL 01Span - whole number

Strany 6 - 1.1 MODEL NUMBER DESIGNATION

Step CommentCAL 06Filter.Fluctuations in the flowrate can be filtered out so thatthe Rate is held steady. The filter value is programmedbetween 1 - 9

Strany 7 - Introduction 5

Step CommentCAL 11Low Alarm - digits after the decimal point.CAL 10 & 11 program the flowrate below which thelow alarm relay will close. The valu

Strany 8 - ≈3.5mA the Model 202A

3.2 CALCULATION OF RATE AND TOTAL3.2.1 Analog InputThe flowrate, R, is calculated as follows:R = SA if the linear relationship is selectedor R = S i

Strany 9

3.2.2 The Cutoff PointBecause many transducers do not always exactly transmit 4mA when they are atzero rate, it is often necessary to define a rate b

Strany 10 - 2. SPECIFICATION

3.3 TOTAL CONVERSIONThe Total Conversion feature enables the rate to be displayed in one engineeringunit (eg. gallons/minute) and the totals to be di

Strany 11

3.4 FILTERINGFrequency fluctuations caused by pulsating flow through a flowmeter, oftenmakes the Rate impossible to read with any precision. The Mod

Strany 13 - 3.1 PROGRAM STEPS

A 90% 99%1 0 02 1 24 2 46 3 610 5 1115 8 1720 11 2225 14 2835 20 4045 25 5160 34 6975 43 8690 52 10399 57 113Table 1 - Response to a step Input (in s

Strany 14

3.5 EXAMPLEA vortex flowmeter has a maximum output of 20.538 litres/min at 20mA. It isrequired to display the flowrate in litres/min with 1 decimal

Strany 15

4. SIGNAL INPUTThe signal input is on terminals 3 and 4 and can be connected as follows:20 Signal Input

Strany 16

5. ALARM & PULSE OUTPUTSOpen collector outputs are provided for high and low flowrate alarms. Theoutput can sink up to 200mA and can be used t

Strany 17

Connections22 Alarm & Pulse Outputs

Strany 18 - 3.3 TOTAL CONVERSION

6. INTRINSIC SAFETY CONNECTIONSWhen installing the Model 202A in hazardous areas, the wiring and installationmust comply with appropriate installat

Strany 19 - 3.4 FILTERING

24 Intrinsic Safety Connections

Strany 20

7. INSTALLATION7.1 WALL MOUNTINGA wall mounting bracket is supplied with each instrument. The bracket shouldbe attached to the wall using round head

Strany 21 - 3.5 EXAMPLE

7.2 PANEL MOUNT VERSIONThe panel mount version of the Model 202A is supplied with two panel mountbrackets and plug-in terminals which are accessible

Strany 22 - 4. SIGNAL INPUT

7.3 REMOVING THE FRONT PANELThe front of the instrument is removed as follows:1. Remove both the top and bottom cover strips (ie. the dark plastic st

Strany 23 - OUTPUTS

CONTENTS1. Introduction 31.1 Model Number Designation 4 1.2 Operation 61.3 Intrinsic Safety Considerations 7 2. Specification 83. Prog

Strany 25 - CONNECTIONS

7.4 THE MAIN ELECTRONICSThe front section of the housing contains the microprocessor and display.It is also possible to adjust the display contrast v

Strany 26

7.5 WIRINGWhen connecting the Model 202A, it is goods practice to use shielded cable.In order to comply with the requirements for Electromagnetic Com

Strany 27 - 7. INSTALLATION

7.6 TERMINAL DESIGNATIONS4-20mA Input3 4-20mA (-)4 4-20mA (+)Outputs5 Low Alarm (-)6 Low Alarm (+)7 High Alarm (-) or Pulse Output (-)8 High Alarm (+

Strany 28 - 7.2 PANEL MOUNT VERSION

Index AAccumulated Total, 6CCAL Sequences, 10Cutoff Point, 11DDecimal Point, 11Display, 8Display Test, 6FFiltering, 17HHi Test, 6High Alarm, 13IInstal

Strany 30 - 28 Installation

1. INTRODUCTION The Model 202A Rate-Totaliser is a microprocessor based instrument designed tomeasure a 4-20mA signal from flowmeters and pressure tra

Strany 31 - 7.4 THE MAIN ELECTRONICS

1.1 MODEL NUMBER DESIGNATIONThe Model Number of an instrument describes which input and output optionsare installed.Model 202 A. 1 0 Input OptionsA

Strany 32 - 7.5 WIRING

The Model 202AIntroduction 5

Strany 33 - 7.6 TERMINAL DESIGNATIONS

1.2 OPERATIONThe Model 202A Rate Totaliser will display:RateResettable TotalAccumulated Total.Both the Rate and Resettable Total are continuously dis

Strany 34

1.3 INTRINSIC SAFETY CONSIDERATIONSThe Model 202A is certified for use in hazardous areas and has both CENELECand CSA NRTL/C approvals.The Model 202A

Komentáře k této Příručce

Žádné komentáře