<Toc> <Ind> <3. PC Link Communication >
3-7
IM 77J01J11-01E
3.2.3 BRR Reading I Relays on a Bit-by-bit Basis in a Random
Order
Function
Reads the ON/OFF statuses of I relays by the specified number of bits in a random order.
The number of bits to be read at a time is 1 to 32.
For the format of response in the event of failure, see subsection 3.1.2.
The command shown below includes the checksum function. When performing
communication without a checksum, do not include the 2-byte checksum command
element in the command.
Command/Response (for normal operation)
Number of Bytes 1 2 213 2 5 1 5 1
Command
Element
STX Address
number
(ADDRESS)
CPU
number
01
0 BRR Number
of bits
(n)
I relay
number 1
Comma
or space
I relay
number 2
Comma
or space
I relay
number n
Checksum ETX CR
5211
Number of Bytes 112 2211 2 11
Response
Element
STX Address
number
(ADDRESS)
CPU
number
01
OK d1 d2 CR dn Checksum ETX
The response is 0 when the status is OFF or 1 when ON.
Command (continued)
dn: reads data of the specified number of bits (n=1 to 32)
dn=0(OFF)
dn=1(ON)
030209E.EPS
Example:
Reading the statuses of alarms-1 and -2 of the VJ Series signal conditioner with communi-
cation address-1
The following command reads the statuses of alarm-1 (
I0009) and alarm-2 (I0010) at
communication address-1.
[Command]
[STX]01010BRR02I0009,I001082[ETX][CR]
With respect to the above command, the ON and OFF responses are returned for alarms-1
and -2 respectively.
[Response]
[STX]0101OK10BD[ETX][CR]
Alarm-1 has been ON.
030210E.EPS