The MSG Read instruction on Rung 0000 is configured as follows:
On the ―General‖ tab, in the ―This Controller‖ area, enter the Channel (1 for Ethernet), Communication Command
(500CPU Read), Data Table Address (B3:0), and the Size in Elements (number of data words) (5). In the ―Target Device‖
area, enter the starting data table address of the MW100 (N30:0 for Communication Channel C001). Enter ―RI11:0‖ for the
Routing Information File (RI). PLC Data File R1:11 will automatically be created in the MicroLogix 1100. Then click on the
―MultiHop tab at the top of the Setup Screen.
In the ―To Address‖ area, enter the IP address of the MW100 (192.168.1.200). Then click on the close window (X) at the
top right of the Setup Screen (the screen can also be closed by clicking on the ―Setup Screen‖ In the MSG instruction. The
MSG Write to the MW100 is now complete.