2-18
IM04L41B01-65EN
Batch
Click here (also selectable from [Setting] - [Engineering Mode Setting]).
Automatically increase the lot number by 1 at Memory Stop.
Use the lot number indication.
Header 1 to 3
Enter character strings (up to 64 characters) that are written to the batch and continuous
data files.
Calibration Correction
Canonlybespecifiedonmeasurementchannels.
Click here (also selectable from [Setting] - [Engineering Mode Setting]).
Set point number
Enter values.
Select the number of set
points.
Select channel.
Number of Set Points
Select the number of set points from [OFF] or [2] to [16].
Select [OFF] if you are not using the correction function.
Selectable Range of Measured and True Values
Channelsthataresettoscalingorsquarerootcomputation:–30000to30000(the
decimal point position depends on the channel setting)
All other channels: Selectable range in the specified range
For the measured value, set a value that is greater than the previous measured value. If
you enter a setting that does not meet these conditions, the [Number of Set Points] is set
to [OFF] when you store the setup data, print the setup data, or send the setup data to
theDXPusingtheCommunicator.
2.5 Confiuring the Engineering Mode