When calibrating the output range of the 8-CH, Medium-Speed Analog Output module
All eight channels are calibrated at Zero (0 V) and Full (10 V).
Digital multimeter
H
L
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
Calibration of Temperature Measurements using Thermocouples
Required Instruments
DC Voltage/Current Standard
Must meet the following specifications (5520A by FLUKE or equivalent):
Output accuracy: ±(0.005%+1 µV) or less
0 °C reference temperature device
Must meet the following specifications (ZC-114/ZA-10 by Coper Electronics or
equivalent)
Standard temperature stability accuracy: ±0.05°C or less
4.4 Calibration