User’sManualYTA Series Temperature TransmitterFieldbus CommunicationIM 01C50T02-01EIM 01C50T02-01E8th Edition
<3. About Fieldbus>3-2IM 01C50T02-01E3.4 Wiring System CongurationThe number of devices that can be connected to a single bus and the cab
<4. Getting Started>4-1IM 01C50T02-01E4. Getting StartedFieldbus is fully dependent upon digital communication protocol and differs in ope
<4. Getting Started>4-2IM 01C50T02-01E4.2 Host SettingTo activate Fieldbus, the following settings are required for the host.IMPORTANTDo n
<4. Getting Started>4-3IM 01C50T02-01E4.4 Integration of DDIf the host supports DD (Device Description), the DD of the YTA needs to be ins
<5. Conguration>5-1IM 01C50T02-01E5. CongurationThis chapter contains information on how to adapt the function and performance of the YT
<5. Conguration>5-2IM 01C50T02-01E5.2 Network DenitionBefore connection of devices with Fieldbus, dene the Fieldbus network. Allocate P
<5. Conguration>5-3IM 01C50T02-01E5.3 Denition of Combining Function BlocksThe input/output parameters for function blocks are combined.
<5. Conguration>5-4IM 01C50T02-01E5.4 Setting of Tags and AddressesThis section describes the steps in the procedure to set PD Tags and
<5. Conguration>5-5IM 01C50T02-01ETable 5.4 VCR Static EntrySub-indexParameter Description1 FasArTypeAndRole Indicates the type and role
<5. Conguration>5-6IM 01C50T02-01E5.6 Block SettingSet the parameter for function block VFD.5.6.1 Link ObjectLink object combines the da
1IM 01C50T02-01EYTA seriesTemperature Transmitter Fieldbus CommunicationIM 01C50T02-01E 8th EditionCONTENTS1. Introduction ...
<5. Conguration>5-7IM 01C50T02-01E5.6.3 View ObjectThis is the object to form groups of parameters in a block. One of advantage brought b
<5. Conguration>5-8IM 01C50T02-01ETable 5.12 View Object for Transducer BlockRelative indexParameterVIEW 1 VIEW 2 VIEW 3 VIEW 4 (1st)VIEW
<5. Conguration>5-9IM 01C50T02-01ERelative indexParameterVIEW 1 VIEW 2 VIEW 3 VIEW 4 (1st)VIEW 4 (2nd)VIEW 4 (3rd)VIEW 4 (4th)VIEW 4 (5th)
<5. Conguration>5-10IM 01C50T02-01ERelative indexParameterVIEW 1 VIEW 2 VIEW 3 VIEW 4 (1st)VIEW 4 (2nd)VIEW 4 (3rd)VIEW 4 (4th)VIEW 4 (5th
<5. Conguration>5-11IM 01C50T02-01ETable 5.13 View Object for AI Function BlockRelative indexParameterVIEW1VIEW2VIEW3VIEW41 ST_REV 2 2 2
<5. Conguration>5-12IM 01C50T02-01E5.6.4 Parameters of Transducer BlockThe transducer block makes settings for the temperature transmitte
<5. Conguration>5-13IM 01C50T02-01E If you want to switch back to select sensor 1 input while the backup action is active after the senso
<5. Conguration>5-14IM 01C50T02-01E CAL_POINT_HI_1 (2), CAL_POINT_LO_1 (2) These parameters store the calibrated upper and lower range l
<5. Conguration>5-15IM 01C50T02-01E PV_FTIMEStipulates the time constant (in seconds) of the rst-order lag lter inside the AI block.
<6. In-process Operation>6-1IM 01C50T02-01E6. In-process Operation6.1 Mode TransitionAll function blocks have modes. All blocks have the
2IM 01C50T02-01E5.6.4 Parameters of Transducer Block ...5-125.6.5 Parameters of AI Function Block
<6. In-process Operation>6-2IM 01C50T02-01ETable 6.1 Alert ObjectSubindexParameter NameExplanation Analog AlertDiscreteAlertUpdateAlert1 1
<6. In-process Operation>6-3IM 01C50T02-01EFollowing gure shows the items shown on a display.F0603.ai(5)(3)(2)(1)(4)Figure 6.3 LCD Displa
<7. Errors and Warnings>7-1IM 01C50T02-01E7. Errors and Warnings7.1 Error and Warning IndicationsFaults found as a result of self-diagnos
<7. Errors and Warnings>7-2IM 01C50T02-01ECode Displayed on LCDIndication of DEVICE_STATUS_#Cause RemedyAL032 Not Used Sensor2 Although a c
<7. Errors and Warnings>7-3IM 01C50T02-01ETable 7.2 WarningsCode Displayed on LCDIndication of DEVICE_STATUS_#Cause RemedyAL100 AI1 in O/S
<7. Errors and Warnings>7-4IM 01C50T02-01ECode Displayed on LCDIndication of DEVICE_STATUS_#Cause RemedyAL150 PID2 in Bypass active The byp
<7. Errors and Warnings>7-5IM 01C50T02-01E7.3 Checking with DEVICE_STATUS_1 to _8 of Resource BlockWhen faults occur, the corresponding bi
<7. Errors and Warnings>7-6IM 01C50T02-01ETable 7.5 Contents of DEVICE_STATUS_2Hexadecimal IndicationIndication When Device Description Ha
<7. Errors and Warnings>7-7IM 01C50T02-01ETable 7.7 Contents of DEVICE_STATUS_5Hexadecimal IndicationIndication When Device Description Ha
<7. Errors and Warnings>7-8IM 01C50T02-01ETable 7.9 Contents of DEVICE_STATUS_7Hexadecimal IndicationIndication When Device Description Ha
3IM 01C50T02-01EAppendix 4. PID Block ...A4-1A4.1 Function Diagram .
<7. Errors and Warnings>7-9IM 01C50T02-01ETable 7.11 Example of Warning Masking SettingsCase Device CongurationsWARNING_ ENABLE_1WARNING_
<8. Handling Caution>8-1IM 01C50T02-01E8. Handling CautionThis chapter describes important cautions regarding the installation of explosio
<8. Handling Caution>8-2IM 01C50T02-01ENote 2. Wiring* All wiring shall comply with Canadian Electrical Code Part I and Local Electrical Co
<8. Handling Caution>8-3IM 01C50T02-01E* When combined with FISCO model IIC barrier Ui = 17.5 V, Ii = 360 mA, Pi = 2.52 W, Ci = 1.5 nF, L
<8. Handling Caution>8-4IM 01C50T02-01ESupply unitThe supply unit must be certied by a notify body as FISCO model and following trapezoida
<8.HandlingCaution>8-5IM 01C50T02-01ESensor circuitEEx ia IIC T4Maximum Voltage (Uo) = 7.7 VMaximum Current (Io) = 70 mAMaximum Power (Po
<8.HandlingCaution>8-6IM 01C50T02-01E(2) ElectricalConnectionThe type of electrical connection is stamped near the electrical connectio
<8. Handling Caution>8-7IM 01C50T02-01E *1: The production year The third gure from the left of the serial number shows the year of pr
<8. Handling Caution>8-8IM 01C50T02-01E IFM018-A12 Installation Diagram(Intrinsically safe, Division 1 Installation)Non Hazardous Locat
<8. Handling Caution>8-9IM 01C50T02-01EThe allowed voltage Uo of the associated apparatus used to supply the bus is limited to the range of
<1. Introduction>1-1IM 01C50T02-01E1. IntroductionThis manual contains a description of the YTA320 Temperature Transmitter Fieldbus Commun
<8. Handling Caution>8-10IM 01C50T02-01E*4: Associated Nonincendive Field Wiring Apparatus manufacturer’s installation drawing must be fol
<8. Handling Caution>8-11IM 01C50T02-01E Installation Diagram(Installation Diagram for Intrinsically Safe)Non Hazardous LocationHazardous
<8. Handling Caution>8-12IM 01C50T02-01ESupply unitTrapezoidal or rectangular output characteristic only Uo = 14...24 V (I.S. maximum valu
<8. Handling Caution>8-13IM 01C50T02-01EElectrical Data:• Supply Input (+ and –) Maximum Input Voltage Ui: 32 V Maximum Internal Capacita
<9. General Specications>9-1IM 01C50T02-01E9. General Specications9.1 Standard SpecicationsFor items other than those described below,
<9.GeneralSpecications>9-2IM 01C50T02-01E9.2 OptionalSpecicationsForitemsotherthanthosedescribedbelow,refertoIM01C50B01-01E
<9. General Specications>9-3IM 01C50T02-01ETable 9.1 AccuracySensor TypeReferenceStandardMeasurement RangeMinimum Span(Recommended)Accura
<9. General Specications>9-4IM 01C50T02-01ETable 9.2 Ambient Temperature Effect (/10°C Chang)Sensor TypeInput RangeA/D Coefcient °C °FT/
<Appendix 1. List of Parameters for Each Block of the YTA>A1-1IM 01C50T02-01EAppendix 1. List of Parameters for Each Block of the YTANote:
<Appendix 1. List of Parameters for Each Block of the YTA>A1-2IM 01C50T02-01ERelative IndexIndex Parameter Name Factory DefaultWrite ModeEx
<1. Introduction>1-2IM 01C50T02-01E For Safe Use of ProductFor the protection and safety of the operator and the instrument or the system
<Appendix 1. List of Parameters for Each Block of the YTA>A1-3IM 01C50T02-01ERelative IndexIndex Parameter Name Factory DefaultWrite ModeEx
<Appendix 1. List of Parameters for Each Block of the YTA>A1-4IM 01C50T02-01ERelative IndexIndexParameter NameFactory DefaultWrite ModeExpl
<Appendix 1. List of Parameters for Each Block of the YTA>A1-5IM 01C50T02-01ERelative IndexIndexParameter NameFactory DefaultWrite ModeExpl
<Appendix 1. List of Parameters for Each Block of the YTA>A1-6IM 01C50T02-01ERelative IndexIndexParameter NameDefault (factory setting)Writ
<Appendix 1. List of Parameters for Each Block of the YTA>A1-7IM 01C50T02-01EA1.4 Transducer Block Relative IndexIndex Parameter NameDefau
<Appendix 1. List of Parameters for Each Block of the YTA>A1-8IM 01C50T02-01ERelative IndexIndex Parameter NameDefault (factory setting)Wri
<Appendix 1. List of Parameters for Each Block of the YTA>A1-9IM 01C50T02-01ERelative IndexIndex Parameter NameDefault (factory setting)Wri
<Appendix 1. List of Parameters for Each Block of the YTA>A1-10IM 01C50T02-01ERelative IndexIndex Parameter NameDefault (factory setting)Wr
<Appendix 1. List of Parameters for Each Block of the YTA>A1-11IM 01C50T02-01ERelative IndexIndex Parameter NameDefault (factory setting)Wr
<Appendix 1. List of Parameters for Each Block of the YTA>A1-12IM 01C50T02-01ERelative IndexIndex Parameter NameDefault (factory setting)Wr
<1. Introduction>1-3IM 01C50T02-01E ATEX DocumentationThis procedure is only applicable to the countries in European Union.GBDKIENLSFPFDSL
<Appendix 2. Parameters for Basic Settings, and How to Make and Change the Settings>A2-1IM 01C50T02-01EAppendix 2. Parameters for Basic Settin
<Appendix 2. Parameters for Basic Settings, and How to Make and Change the Settings>A2-2IM 01C50T02-01ETo Do This Corresponding Parameters Outl
<Appendix 2. Parameters for Basic Settings, and How to Make and Change the Settings>A2-3IM 01C50T02-01E(1) Making the Input Sensor SettingsAcc
<Appendix 2. Parameters for Basic Settings, and How to Make and Change the Settings>A2-4IM 01C50T02-01EAccess the parameter CAL_STATE_1 and set
<Appendix 2. Parameters for Basic Settings, and How to Make and Change the Settings>A2-5IM 01C50T02-01EAccess the parameter SENSOR_TYPE_1 and s
<Appendix 2. Parameters for Basic Settings, and How to Make and Change the Settings>A2-6IM 01C50T02-01E(5) Setting the Low Cut-off LevelSet th
<Appendix 3. Function Block Diagram>A3-1IM 01C50T02-01EAppendix 3. Function Block Diagram A3.1 AI Block Function DiagramFA0301.aiAITransd
<Appendix 4. PID Block>A4-1IM 01C50T02-01EAppendix 4. PID BlockA PID block performs the PID control computation based on the deviation of
<Appendix 4. PID Block>A4-2IM 01C50T02-01EA4.3 Parameters of PID BlockNOTE: In the table below, the Write column shows the modes in which
<Appendix 4. PID Block>A4-3IM 01C50T02-01EIndex Parameter NameDefault (factory setting)Write Valid Range Description32 RCAS_IN 0 Remote se
<2. Part Names>2-1IM 01C50T02-01E2. Part NamesRefer to the individual instruction manuals for detailed descriptions of the parts. This sec
<Appendix 4. PID Block>A4-4IM 01C50T02-01EIndex Parameter NameDefault (factory setting)Write Valid Range Description61 HI_ALM — — As abo
<Appendix 4. PID Block>A4-5IM 01C50T02-01EA4.5.1 Velocity Type Output ActionThe PID block determines the value of the new control output O
<Appendix 4. PID Block>A4-6IM 01C50T02-01EBlock Mode DescriptionROut Remote output mode, in which the PID block outputs the value set in RO
<Appendix 4. PID Block>A4-7IM 01C50T02-01ESetpoint Rate LimitsThe setpoint rate limits are used to restrict the magnitude of changes in the
<Appendix 4. PID Block>A4-8IM 01C50T02-01EA4.14 Initialization and Manual Fallback (IMan)Initialization and manual fallback denotes a set
<Appendix 4. PID Block>A4-9IM 01C50T02-01EA4.17 Mode Shedding upon Computer FailureWhen the data status of RCAS_IN or ROUT_IN, which is th
<Appendix 4. PID Block>A4-10IM 01C50T02-01EA4.19 Example of Block ConnectionsPIDBKCAL_IN OUTINAOBKCAL_OUTCAS_INAIOUTFA0406.aiWhen conguri
<Appendix 4. PID Block>A4-11IM 01C50T02-01ERelative IndexParameter MnemonicVIEW 1VIEW 2VIEW 3VIEW 434 SHED_OPT 135 RCAS_OUT 536 ROUT_OUT 53
<Appendix 5. Link Master Functions>A5-1IM 01C50T02-01EAppendix 5. Link Master FunctionsA5.1 Link Active SchedulerA link active scheduler
<Appendix 5. Link Master Functions>A5-2IM 01C50T02-01EA5.3 Transfer of LASThere are two procedures for an LM to become the LAS: • If the
<3. About Fieldbus>3-1IM 01C50T02-01E3. About Fieldbus3.1 OutlineFieldbus is a bi-directional digital communication protocol for eld dev
<Appendix 5. Link Master Functions>A5-3IM 01C50T02-01E(3) In the LAS settings of the YTA, set the values of V(FUN) and V(NUN) so that they
<Appendix 5. Link Master Functions>A5-4IM 01C50T02-01EA5.5 LM ParametersA5.5.1 LM Parameter ListThe tables below show LM parameters of a
<Appendix 5. Link Master Functions>A5-5IM 01C50T02-01EIndex (SM)Parameter Name Sub-parameter Name (Sub Index)Default Factory SettingAccess
<Appendix 5. Link Master Functions>A5-6IM 01C50T02-01EA5.5.2 Descriptions for LM ParametersThe following describes LM parameters of a YTA
<Appendix 5. Link Master Functions>A5-7IM 01C50T02-01ESub-indexElementSize [bytes]Descrip-tion1 SlotTime 2 V(ST)2 PerDlpduPhlOverhead 1 V(P
<Appendix 5. Link Master Functions>A5-8IM 01C50T02-01E(12) LinkScheduleActivationVariableWriting the version number of an LAS schedule, whi
<Appendix 5. Link Master Functions>A5-9IM 01C50T02-01EA5.6 FAQsQ1. When the LAS stops, a YTA does not back it up by becoming the LAS. Wh
iIM 01C50T02-01ERevision Information Title : YTA series Temperature Transmitter Fieldbus Communication Manual No. : IM 01C50T02-01EEdition D