Yo kogawa Electric CorporationUser’sManualYTA seriesTemperature Transmitter(HART Protocol)IM 01C50T01-01EIM 01C50T01-01E5th Edition
IM 01C50T01-01E2-22. HART COMMUNICATOR OPERATION2.2 Basic Operation of the HART Communicator (Model 275)2.2.1 Keys and FunctionsLCD (Liquid crystal d
2. HART COMMUNICATOR OPERATIONIM 01C50T01-01E2-32.2.2 DisplayThe HART communicator searches for transmitter onthe 4 to 20 mA loop when it is turned o
IM 01C50T01-01E2-42. HART COMMUNICATOR OPERATION • To return to the previous display, press the key.* If ABORT, ESC and EXIT are displayed, press th
2. HART COMMUNICATOR OPERATIONIM 01C50T01-01E2-5YTA :YOKOGAWATag YOKOGAWA FIC-1AHELP DEL ESCENTER5Display OperationYTA :YOKOGAWABasic setup 1 Tag
3. OPERATIONIM 01C50T01-01E3-13. OPERATIONIMPORTANTDo not turn off the power to the transmitterimmediately after transfer of the data from HARTCommun
3. OPERATIONIM 01C50T01-01E3-2Table 3.1 Parameters listItem Description PageHARTCommunicatorTag number, up to 8 charactersExtension of Tag, up to 8 c
3. OPERATIONIM 01C50T01-01E3-3Item Description PageHARTCommunicatorSelect the output direction/value upon Sensor failure from Low, High, off or user-
3. OPERATIONIM 01C50T01-01E3-43.2 Menu Tree1.Device setup2.PV 3.PV AO 4.PV LRV5.PV URV1.Process variables2.Diag/Service3.Basic setup4.Detailed setup5
3. OPERATIONIM 01C50T01-01E3-53.3 ReviewBefore starting operation, review all the configurationof the transmitter to confirm that it meets the curren
3. OPERATIONIM 01C50T01-01E3-6Example: To set Pt100, 4-wire sensor as “Sensor1” input. Also set a unit for Sensor1 as “°C”.YTA : Snsr 1 config 1. S
Blank Page
3. OPERATIONIM 01C50T01-01E3-7YTA : PV is Snsr1 SV is Term TV is Not used 4V is Not usedPressing 'OK' to change them.HELP SAVE ABORT OK1YTA
3. OPERATIONIM 01C50T01-01E3-8— Differential Direction — (For YTA320)If “Diff” is selected as Process variables, it is necessaryto set which is desig
3. OPERATIONIM 01C50T01-01E3-93.4.4 PV RangeThe range for PV corresponding to the 4 to 20mAoutput signal is set at the factory before shipment.Follow
3. OPERATIONIM 01C50T01-01E3-10(2) Changing the range while applying anactual input – Apply values –This feature allows the lower and upper rangeva
3. OPERATIONIM 01C50T01-01E3-113.4.6 Tag No.To change the Tag, see section 2.2.4 “Entering, settingand Sending Data”.Up to 8 characters can be set wi
3. OPERATIONIM 01C50T01-01E3-12During sensor burn out time, the Sensor1 failure or theSensor2 failure error message is generated. (SeeSection 3.6.1 f
3. OPERATIONIM 01C50T01-01E3-13Process, Type:Display Process Variablename and Sensor Type inturn.Type, Wire:Display Sensor Type andthe number of wire
3. OPERATIONIM 01C50T01-01E3-143.5.5.3 Software Write Protect Function● To activate write protect function1. Press Hot key and select “2. Wrt protec
3. OPERATIONIM 01C50T01-01E3-152. Call up the “Snsr1 inp trim” display. [1.Devicesetup → 2. Diag/Service → 3.Calibration →3.Sensor Trim → 1.Snsr 1 in
3. OPERATIONIM 01C50T01-01E3-16Example: To adjust using a voltmeter.Procedures1. Call up the “Scaled D/A trim” display. [1.Devicesetup → 2.Diag/Servi
CONTENTSIM 01C50T01-01EiFD No. IM 01C50T01-01E5th Edition: Sep. 2006 (KP)All Rights Reserved, Copyright © 1998, Yokogawa Electric CorporationCONTENTS1
3. OPERATIONIM 01C50T01-01E3-171. Call up the “HART output” display. [1.Devicesetup → 4.Detailed setup → 3.Output condition →2.HART output]2. Select
3. OPERATIONIM 01C50T01-01E3-18NOTE1. This function is effective only in three kinds ofsensors; Pt100, Pt200 and Pt500.2. Input relations between the
3. OPERATIONIM 01C50T01-01E3-19iimmediately. Warnings are the light errors andindication of the status which is important for opera-tion.When an erro
3. OPERATIONIM 01C50T01-01E3-20Table 3.4 List of ErrorsIndicatorHART display CauseOutput operation upon errorActionN/A GoodEr-01 Output Too LowEr-02
3. OPERATIONIM 01C50T01-01E3-21Table 3.5 List of WarningsThe LRV setting is lower than the temperature range (GS guaranteed value).The LRV setting is
3. OPERATIONIM 01C50T01-01E3-223.6.2 WarningsWhen non-fatal errors or unusual status such as invalidsetting of parameters has happened, it can be det
4. PARAMETERS LISTSIM 01C50T01-01E4-14. PARAMETERS LISTSInitial setting value marked with “ * ” is as of specified upon ordering.Item Selection/ Sett
IM 01C50T01-01E4-24. PARAMETERS LISTS(1)PV (2)SV (3)TV (4)4V (5)PV,SV (6)PV,SV,TV (7)PV,SV,TV,4V (8)Inhibit(1)mA (2)% (3)mA,% (4)InhibitShow or Inhib
APPENDIX A. SAFETY INSTRUMENTED SYSTEMS INSTALLATIONIM 01C50T01-01EA-1APPENDIX A. SAFETY INSTRUMENTEDSYSTEMS INSTALLATIONWARNINGThe contents of this
IM 01C50T01-01EA-2APPENDIX A. SAFETY INSTRUMENTED SYSTEMS INSTALLATION Table A.2.5 Proof TestingTesting method Tools requiredTA0102.EPSEx
CONTENTSIM 01C50T01-01EiiAPPENDIX A. SAFETY INSTRUMENTED SYSTEMS INSTALLATION ... A-1A.1 Scope and Purpose ...
APPENDIX A. SAFETY INSTRUMENTED SYSTEMS INSTALLATIONIM 01C50T01-01EA-3A.2.9 Reliability DataA detailed Failure Mode, Effects, and DiagnosticsAnalysis
◆ Revision Record● Manual No. : IM 01C50T01-01E● Title : YTA series Temperature Transmitter (HART Protocol)Edition Date Page Revised item1st2nd3rd4th5
Blank Page
IM 01C50T01-01E1-11. INTRODUCTION1. INTRODUCTIONThank you for purchasing the YTA series TemperatureTransmitter.The YTA series Temperature Transmitter
IM 01C50T01-01E1-21. INTRODUCTION䊏 For Safe Use of ProductFor the protection and safety of the operator and theinstrument or the system including the
IM 01C50T01-01E1-31. INTRODUCTION䊏 ATEX DocumentationThis procedure is only applicable to the countries inEuropean Union.GBAll instruction manuals fo
IM 01C50T01-01E1-41. INTRODUCTION1.1 Matching of DD and Instru-mentsTo setup the YTA via HART handheld communicator,it is necessary that the correct
2. HART COMMUNICATOR OPERATIONIM 01C50T01-01E2-12. HART COMMUNICATOR OPERATION2.1 Conditions of Communica-tion Line2.1.1 Interconnection Between YTAa