<Toc> <Ind> <3. PC Link Communication >
3-11
IM 77J04J11-01E 1st Edition : 2006.08.25-00
BRS Specifies I relays to be monitored on a bit-by-bit basis
Function
Specifies the I-relay numbers to be monitored on a bit-by-bit basis. Note that this com-
mand simply specifies I relays. Actual monitoring is performed by the BRM command after
the I relay numbers are specified by this command.
When the volume of data is large and you wish to increase the baud rate, it is effective to
use a combination of the BRS and BRM commands rather than just the BRR command.
If the power supply is turned off, the specified I-relay numbers will be erased.
The number of I relays to be specified at a time is 1 to 32.
For the format of response in the event of failure, see subsection 3.1.2.
The command shown below includes the checksum function.
When performing communication without checksum, do not include the 2-byte
checksum element in the command.
Command/Response (for normal operation)
Number of Bytes 1 2 2 1 3 2 5 1 5 1
Command
element
STX Address
number
(ADR)
CPU
number
01
0 Number
of bits
(n)
I relay
number 1
BRS Comma
or space
I relay
number 2
Comma
or space
Command (continued)
5211
I relay
number n
Checksum ETX CR
12 22 2 11Number of Bytes
Response
element
STX Address
number
(ADR)
CPU
number
01
OK Checksum ETX CR
Example:
Specifying that the burnout, alarm 1 and alarm 2 of the M Series with address number 01
are to be monitored.
(This command simply specifies the registers to be monitored.)
[Command]
[STX]01010BRS03I0007,I0001,I0002B9[ETX][CR]
OK is returned in response to the above command.
[Response]
[STX]0101OK5C[ETX][CR]