Yokogawa JUXTA M Series Digital Limit Alarms MVTK Uživatelský manuál Strana 29

  • Stažení
  • Přidat do mých příruček
  • Tisk
  • Strana
    / 70
  • Tabulka s obsahem
  • KNIHY
  • Hodnocené. / 5. Na základě hodnocení zákazníků
Zobrazit stránku 28
<Toc> <Ind> <3. PC Link Communication >
3-15
IM 77J04J11-01E 1st Edition : 2006.08.25-00
WRR Reads D registers and I relays on a word-by-word basis in random
order
Function
Reads the statuses of the individul registers on a word-by-word basis specified in random
order by the specified number of words.
The number of words to be read at a time is 1 to 32.
For the format of response in the event of failure, see subsection 3.1.2.
The command shown below includes the checksum function.
When performing communication without checksum, do not include the 2-byte
checksum element in the command.
Command/Response (for normal operation)
Number of Bytes 1 2 2 1 3 2 5 1 5 1
Command
element
STX Address
number
(ADR)
CPU
number
01
0 WRR Number
of words
(n)
Register
number 1
Comma
or space
Register
number 2
Comma
or space
Command (continued)
1 2 224 4 4 2 11Number of Bytes
Response
element
STX Address
number
(ADR)
CPU
number
01
OK dddd1 dddd2 ETX CR ddddn Checksum
The response is returned in a 4-digit character string (0000 to FFFF) in hexadecimal.
ddddn: read data of the specified number of words
ddddn is a character string in hexadecimal.
n=1 to 32
5211
Register
number n
ETX CR Checksum
Example:
Reading the alarm-1 setpoint (D0101) and alarm-2 setpoint (D0102) of the M Series with
address number 01.
[Command]
[STX]01010WRR02D0101,D010288[ETX][CR]
The alarm-1 setpoint 500 (01F4 [HEX]) and alarm-2 setpoint 500 (01F4 [HEX]) are re-
turned with respect to the above command (50.0 is expressed as 500).
[Response]
[STX]0101OK01F401F4FC[ETX][CR]
500 in decimal
(Alarm-1 setpoint is 50.0.)
500 in decimal
(Alarm-2 setpoint is 50.0.)
Zobrazit stránku 28