3-16
<Toc> <Ind> <3. PC Link Communication >
IM 77J04J11-01E 1st Edition : 2006.08.25-00
WRW Writes data into D registers and I relays on a word-by-word basis in
random order
Function
Writes register data specified for each register into the registers specified in random order
by the specified number of words.
The number of words to be written into at a time is 1 to 32.
For the format of response in the event of failure, see subsection 3.1.2.
The command shown below includes the checksum function.
When performing communication without checksum, do not include the 2-byte
checksum element in the command.
Command/Response (for normal operation)
Number of Bytes 1 2 2 1 3 2 5 1 4 1
Command
element
STX Address
number
(ADR)
CPU
number
01
0 WRW dddd1Number
of words
(n)
Register
number 1
Comma
or space
Comma
or space
Checksumdddd2 ETX CR
4
Register
number 2
Comma
or space
51
ddddn
42
Register
number n
Comma
or space
51 11
Number of Bytes 1 2 2 2 2 1 1
Response
element
STX Address
number
(ADR)
CPU
number
01
OK CRChecksum ETX
Write data is specified in a 4-digit character string (0000 to FFFF) in hexadecimal.
Command (continued)
ddddn: write data of the specified number of words
ddddn is a character string in hexadecimal.
n=1 to 32
Example:
Writing 20.0 and 15.0 into the alarm-1 setpoint (D0101) and alarm-2 setpoint (D0102) of the M
Series with address number 10 respectively.
[Command]
[STX]10010WRW02D0101,00C8,D0102,00968F[ETX][CR]
200 in decimal
(Alarm-1 setpoint is 20.0.)
150 in decimal
(Alarm-2 setpoint is 150.0.)
OK is returned in response to the above command.
[Response]
[STX]1001OK5C[ETX][CR]