Yokogawa Standalone MW100 Uživatelský manuál Strana 11

  • Stažení
  • Přidat do mých příruček
  • Tisk
  • Strana
    / 131
  • Tabulka s obsahem
  • KNIHY
  • Hodnocené. / 5. Na základě hodnocení zákazníků
Zobrazit stránku 10
- 11/131 -
IM MW100-S16E-1
Ed01
Period of integrity/event poll and publishing commands are configurable at MW100.
Parameters for controlling DNP master/client behavior is shown in Table 4.
Table 4. Parameters for controlling DNP master/client behavior
Kind Configuration
Integrity Poll Period and publishing commands for polling static data
- period is configurable within 1 to 3600 [s]
- class read :
- selectable from “Off”, “Class 0”, “Class 0, 1, 2, 3”
- publishing command :
- Max. 100 entries
Event Poll Period and publishing commands for polling event data
- period is configurable within 1 to 3600 [s]
- class read :
- selectable from “Off”, “Class 1, 2, 3”, “Class 0, 1, 2,3”
Zobrazit stránku 10
1 2 ... 6 7 8 9 10 11 12 13 14 15 16 ... 130 131

Komentáře k této Příručce

Žádné komentáře