2.2.1. DNP master/client specification
Basic specification of DNP master/client functions is shown in Table 5.
Table 5. Basic specification of DNP master/client functions
Item Specification
Accessible objects Binary Input (1)
Double-bit (3)
Binary Output (10)
Counter (20)
Analog Input (30)
Analog Output (40)
Class (60)
Configurable destinations Max. 10 units
Configurable commands Max. 100 commands
Period of integrity poll Configurable within 1 to 3600 [s]
Period of event poll Configurable within 1 to 3600 [s]
Using unsolicited message Configurable per destination (OFF, ON)
Available datalink Serial (RS-232, 422/485), Ethernet (TCP/IP)
Supported commands Read
Select
Operate
Direct Operate
Direct Operate NR
Write
Enable Unsolicited
Disable Unsolicited