
IM 1E10C1-E
7-12
7. OPERATION VIA HART COMMUNICATOR
7.3.4 Setting Parameters
The three parameters must be set to obtain a correct signal.
Nominal size, flow span and meter factor must be set.
(1) Nominal Size
The nominal size is engraved on the data plate of the combined flow tube.
1. Device setup 4. Detailed setup 1. Sensor 4. Sensor config 1. Size unit
ADMAG SE :
Size unit
mm
mm
in
DEL DEL ESC ENTER
1
2
Select “in” (inch).
Press ENTER (F4).
Press SEND (F2) to set data to the ADMAG SE.
ADMAG SE :
Sensor config
1 Size unit in
2 Line size
3 MF
4 Auto zero
5 Flow dir
HELP SEND HOME ENTER
3
Call up “Size unit” setting display.
ADMAG SE :
Size unit
mm
mm
in
DEL DEL ESC ENTER
4. Sensor config 3. Line size
ADMAG SE :
Line size
10.00 in
10.00
DEL DEL ESC ENTER
1
F4
2
Enter “2” with alphanumeric keys.
Press ENTER (F4).
Press SEND (F2) to set data to the ADMAG SE.
By pressing HOME (F3), the display returns to “Online
Menu.”
ADMAG SE :
Sensor config
1 Size unit in
2 Line size
3 MF
4 Auto zero
5 Flow dir
HELP SEND HOME ENTER
3
(ENTER)
F2
(SEND)
Call up “Line size” setting display.
‘2’
ADMAG SE :
Line Size
10.00
2
DEL DEL ESC ENTER
Example: Set “2 inch”.
1. Size unit
2. Line size
F4
(ENTER)
F2
(SEND)
NOTE
Komentáře k této Příručce