6. OUTLINE
STANDARD SPECIFICATIONS
Refer to IM 01E20F02-01E for FOUNDATION Fieldbus
communication type and IM 01E20F12-01E for
PROFIBUS PA communication type marked with “
Converter (Integral flowmeter)
The contents of (*1) and (*2) described in the converter
specifications are follows.
*1: Select two points from: one pulse output, one alarm
output, one status input, or two status outputs.
*2: For models without an indicator, the configuration tool
(Such as HTT (handheld terminal) or FieldMate
TM
, etc.)
is necessary to set parameters.
Excitation Method:
• Standard dual frequency excitation:
Size 2.5 to 400 mm (0.1 to 16 in.)
• Enhanced dual frequency excitation:
Size 25 to 200 mm (1.0 to 8.0 in.)
(Optional code HF1 or HF2)
Input Signal (*1) “”:
One Status Input: Dry contact
Load Resistance: 200 or less (ON), 100 k or more
(OFF)
Output Signals “”:
One Current Output: 4 to 20 mA DC (load resistance:
750 maximum, including cable resistance)
One Pulse Output (*1):
Transistor contact output (open collector)
Contact capacity: 30 V DC (OFF), 200 mA (ON)
Output rate: 0.0001 to 10,000 pps (pulse/second)
One Alarm Output (*1):
Transistor contact output (open collector)
Contact capacity: 30 V DC (OFF), 200 mA (ON)
Two Status Outputs (*1):
Transistor contact output (open collector)
Contact capacity: 30 V DC (OFF), 200 mA (ON)
Communication Signals “”:
BRAIN or HART communication signal
(Superimposed on the 4 to 20 mA DC signal)
Distance from Power Line: 15 cm (6 in.) or more
(Parallel wiring should be avoided.)
BRAIN:
Communication Distance:
Up to 1.5 km (0.93 miles), when polyethylene insulated
PVC-sheathed cables (CEV cables) are used.
Communication distance varies depending on the type
of cable and wiring used.
Load Resistance:
250 to 450(including cable resistance)
Load Capacitance: 0.22 µF or less
Load Inductance: 3.3 mH or less
Input Impedance of Communicating Device:
10 k or more (at 2.4 kHz)
HART:
Load Resistance:
250 to 600(including cable resistance)
Note: HART is a registered trademark of the HART
Communication Foundation.
Data Security During Power Failure:
Data (parameters, totalizer value, etc.) storage by
EEPROM. No back-up battery required.
Indicator (*2):
Full dot-matrix LCD (32132 pixels)
Lightning Protector:
The lightning protector is built into the current output and
pulse/alarm/status input and output terminals. When
optional code A is selected, the lightning protector is
built into the power terminals.
Protection:
General-purpose Use/Sanitary Type/TIIS Flameproof
type:
IP66, IP67
Explosion proof type except TIIS:
In case of explosion proof type except TIIS, refer to
description of "Enclosure" in "HAZARDOUS AREA
CLASSIFICATION".
Coating:
Case and Cover: Corrosion-resistant coating
Coating Color; Mint green coating (Munsell 5.6 BG
3.3/2.9 or its equivalent)
Converter Material:
Case and Cover : Aluminum alloy
Mounting/Shapes (Integral Flowmeter):
Electrical Connection:ANSI 1/2 NPT female
ISO M20 1.5 female
JIS G1/2 (PF1/2) female
Direction of Electrical Connection: The direction can be
changed even after delivery.
Terminal Connection: M4 size screw terminal
Grounding:
Grounding resistance 100 or less
When optional code A is selected, grounding resis-
tance 10 or less shall be applied.
* In case of explosion proof type except TIIS, follow the
domestic electrical requirements as regulated in each
country.
* In case of TIIS Flameproof type, refer to description of
“HAZARDOUS AREA CLASSIFICATION”.
6. OUTLINE