<8. OPERATION VIA HART CONFIGURATION TOOL (HART 5)>
8-2
IM 01E30D01-01EN
(2) ConrmtheinstalledDDrevisionin
accordance with the procedure of the
CongurationTool.Refertoitsmanualhow
toconrmitindetail.
8.3 InterconnectionbetweenAXRandHARTCongurationTool
TheHARTCongurationToolcaninterfacewiththeAXRfromthecontrolroom,theAXRsite,oranyother
wiringterminationpointintheloop,providedthereisaminimumloadresistanceof250Ωbetweenthe
connectionandthereceivinginstrument.Tocommunicate,itmustbeconnectedinparallelwiththeAXR,and
the connections must be non-polarized. Figure 8.3.1 illustrates the wiring connections for a direct interface at
theAXRsite.TheHARTCongurationToolcanbeusedforremoteaccessfromanyterminalstripaswell.
AXR
F0802.ai
+
‒
SUPPLY
DO
USB
FieldMate
modem
Relaying
terminals
Distributor
Control room
Terminal
board
USB
PC/FieldMate
Figure 8.3.1 Connecting the HART Communicator
Be sure to set parameters as “Protect” on the
writeprotectfunctionafternishofparameter
setting work.
Refer to “Chapter 6 Menu P: Parameter
Protection items” and section “11.3.2” how to use
the write protect function in detail.
Ifthepowerofowmeteristurnedoffwithin30
seconds after parameters have been set, these
settings will be canceled. Accordingly, please
keep the power on for at least 30 seconds after
setting parameters.
Before updating any setting, remember to
always check the parameter content you want
to change as described in Chapter 6: Parameter
Description.
IncaseofHARTConguration,theparameters
are displayed in English only.
Even if the language with the exception of
English is selected at “Language” setting display,
the parameters are displayed in English upon
HARTCongurationTool.
8.2.2 Device Type Manager (DTM) and
Device Revision
WhenconguretheparametersusingFieldMate,
use the DTM (Device Type Manager) referring to
the following table.
MODEL DTM
Name
Device
Type
Device
Revision
AXR A
XRV2.1 AXR(0x57) 2
The device revision can be checked as follows.
DTM Conguration→HART→Flddev
rev