<14. EXPLOSION PROTECTED TYPE INSTRUMENT>
14-2
IM 01E30D01-01EN
Digital Output: ON; 2Vdc, 120mA max., OFF;
30Vdcmax.,4mA,Um=250V
Excitation Circuit: 29 V max.
Enclosure: IP66/IP67
Process Temperature:
Maximum Surface
Temperature
Maximum Process
Temperature
Minimum Process
Temperature
T90°C (+194°F) +70°C (+158°F) 30°C (–22°F)
T110°C (+230°F) +85°C (+185°F) –30°C (–22°F)
T130°C (+266°F) +130°C (+266°F) –30°C (–22°F)
Ambient Temp.: –30°C to +55°C
(–22°F to +131°F)
WARNING
IftheAXRismountedinanareawherethe
use of EPL Db equipment is required, it shall
be installed in such a way that the risk from
electrostatic discharges and propagating brush
dischargescausedbyrapidowofdustis
avoided.
(2) Electrical Connection
The type of electrical connection is stamped near
the electrical connection port according to the
following codes.
ISO M20x1.5 female M
ANSI 1/2NPT female N
F1401.ai
Screw Size Marking
(3) Installation
WARNING
• Groundingresistanceof100Ωorlessis
necessary.
When optional code A is selected, grounding
resistanceof10Ωorlessshallberequired.
All wiring shall comply with local installation
requirements and local electrical code.
In hazardous locations, the cable entry
devicesshallbeofacertiedATEX
ameprooftype,suitablefortheconditionsof
use and correctly installed.
Unused apertures shall be closed with
suitableameproofcertiedblanking
elements.(Theplugattachedisameproof
certied.)
The grounding terminals are located on the inside
and outside of the terminal area.
Connect the cable to grounding terminal in
accordance with wiring procedure 1) or 2).
F1402.ai
1) Internal grounding
terminal
2) External grounding
terminal
Figure 14.1.1 Wiring Procedure for Grounding
Terminals
(4) Operation
WARNING
After de-energizing, delay 5 minutes before
opening.
Take care not to generate mechanical
spark when access to the instrument and
peripheral devices in hazardous locations.
(
5) Maintenance and Repair
WARNING
Theinstrumentmodicationorpartsreplacement
by other than authorized representative of
Yokogawa Electric Corporation is prohibited and
willvoidthecertication.
WARNING
Electrostatic charge may cause an explosion
hazard.
Avoid any actions that cause the generation of
electrostatic charge, such as rubbing with a dry
cloth on coating face of product.