<9. OPERATION VIA HART CONFIGURATION TOOL (HART 7)>
9-4
IM 01E30D01-01EN
9.7 Self-diagnostic Functions
TheHARTcongurationtoolcanbeusedtorun
self-diagnostics on a device and check for incorrect
data settings.
(1) Using DD and DTM
The Self test and Status commands are available
for self-diagnostics. When Self test is run, the
display unit shows an error code and alarm
message if the device detects any illegal parameter
settings or functional faults.
Procedure to call up the Self test display
[Root Menu]→Diagnosis/Service→Test/Status→
Self test
If no error is detected, “Self test OK” is displayed on
thecongurationtool.
Ifthespecicdiagnosticitemisknownforthe
check, you can directly call up the item by using the
Status command.
The status is categorized from 1 to 7. For details,
refer to the table at the end of 9.9.
Showanexamplebelowtoconrmthestatusof
Status group 1.
Procedure to call up the Status display
[Root Menu]Diagnosis/Service→Test/Status→
StatusStatusgroup1
If no error is detected, “Off” is displayed on the
congurationtool.
If there is an error, Onis displayed on the
congurationtool,andacountermeasureforthat
error is necessary.
Example of display: Span > 10 m/s On
Span < 0.3 m/s Off
TTL > 10000 p/s Off
TTL < 0.0001 p/s Off
4-20 Lmt Err Off
9.8 HARTSpecicFunctions
9.8.1 Test Output, Simulation, and Squawk
NOTE
Fixed current output, Flow Simulation Mode,
and Device Variable Simulation Function
continue for a given holding time, then is
released automatically. Even if the HART
congurationtoolpowersupplyisturnedoffor
the communication cable is disconnected, the
test output will continue for that time.
The holding time can be selected from 10 min,
30 min*, 60 min, 3 hour, 6 hour or 12 hour.
*: Default value.
Procedure to call up the display
DD
DTM
[Root Menu]→Diagnosis/
Service→Test→TestTime
(1) Fixed current output
Thisfeaturecanbeusedtooutputaxedcurrent
for loop checks.
Call up the test output parameter (Loop test) and
select the output signal.
Procedure to call up the display
DD
DTM
[Root Menu]→Diagnosis/Service
→Test→Looptest
Display Item Contents
4mA Output a 4mA DC signal
20mA Output a 20mA DC signal
Other Set a desired output signal value
End Exit
(2) Device Variable Simulation Function
Using the simulation function, the output signal can
beconrmedbysettinganyvalueandstatustothe
selected device variable.
Call up the parameter and follow the message
shown.
After completing the step 5, the simulation starts.
The indicator shows output and warning (93: Dev
Sim Wng).